Low Power Server CPUs: the energy saving choice?
- Posted in
- IT Computing
Translated to the datacenter
Before we make any conclusions based upon what we learned in this testing session, we should not forget the lessons learned from previous experiments. And those tests tell us that you should avoid the low end server CPUs: those are the most leaky ones, consuming more power at idle and low load.
Our conclusion on our new energy measurement methodology is:
1. Low power Xeons save power but do not save energy in a typical Hyper-v consolidation ratio. Power is “capped”, but the total energy consumed for a certain task is (more or less) the same.
2. X-series Xeons offer a much better performance per watt ratio, but at the expense of brief power peaks. They do not necessarily need more energy in the long run than the lower power versions, and offer much better response times if your application is CPU bound.
So if you have to pay the actual energy consumption, you have some amp headroom left before being penalized and performance matters to your users, the faster Xeons are the right choice. The benefit is that you can offer a lower response times to your users, even when the CPU is not running at peak load! The Xeon X5670 is more flexible.
In case you pay a fixed price for a fixed amount of amps and you get heavy fines in your mailbox if you briefly breach your amp limit, buying lower power Xeons is probably the way to go.
Then again, we are not very enthusiastic about power capping at the server level. Many companies have already embraced the idea of a Dynamic Scheduled Virtualized Cluster. VMware's vSphere product is the most mature here: it is pretty easy to build a virtual cluster with dynamic power management (DPM) and scheduling (DRS). We still have to investigate this, but if this virtual cluster works well with solutions such as HP Insight Power Manager or Intel’s own power node manager, the faster Xeon will get interesting once again. The basic idea is that you should power cap your entire cluster (or rack), not one server. You should not care that one server needs a little more power than usual, but the whole cluster should not exceed the amp limits described in your contract with the datacenter. That way you can reconcile low response times with low power bills.
A big thanks to Dries Velle for assisting us in the Sizing Servers Lab.